Is that the wire that Electronic Lock connect to access controller can instead by network cable?
Inferior cable will cause too many problems, please pay attention:
Because the large current of eletric locks, (compatible with another access control locks, such as: Access Controller、RFID Reader), if the eletric locks close to the access controller, the cable pressure will be big. Too big cable pressure will make the eletric locks sometimes can be operated, sometimes cannot be operated and the door didn't opened normally. Even, it will occupy the access controller current, then the system will occur restart or stop working situations.
Some peoples use network cable to wiring because of the convenience, but it will cause many trouble, although there is didn't have problems when in adjustment, sometimes after, problems will be happened.
If the cable less than 50m which is from electric locks to acccess controllers,please use the sectional area 1.0mm two-core cable,without shielding, if over than 50m, please add a two-core cable and used together. If over than 100m, we suggest that put the access controller close to the eletric locks, to short the wire distance. The sectional area of natwork cable is 0.2mm, samller 5 times than regular cable,so it is forbidden. The door sensor cable of eletric lock can use network cable.