Please do not use the Network Cable as the Cable for the Electric Lock to the Controller!
2016-11-08 16:52
Details of the problem:

Can the cable of the electric lock be replaced by a network cable?

Expert answer:

The line from the electric lock to the access control board in the access control construction looks very ordinary, but the irregular use of the line can easily cause the failure phenomenon that is difficult to find the cause, this must be paid attention to!

Due to the relatively large working current of various electric locks (compared to other devices in the access control system, such as access control board and access card readers), the electric locks are at a certain distance from the controller, and the voltage drop on the lock wires will be relatively large. If the pressure drop is too large, the electric lock will sometimes be able to move, sometimes not (such as the magnetic lock sometimes has insufficient suction). Shows that the door switch is abnormal. It may even grab current resources with the controller, making the controller insufficient power supply, restarting or even crashing.

Some engineers are convenient for wiring or purchasing, using network cables to wire the electric lock to the controller can easily cause malfunctions, although there seems to be no problem during debugging, problems will often occur after a period of time.

If the cable length from the electric lock to the controller is less than 50 meters, a two-core power cord with a cross-sectional area of 1.0 square millimeter is required, and no shielding is required, if it exceeds 50 meters, please double and add a two-core power cord for parallel power supply. If the cable length is greater than 100 meters, it is recommended to move the controller closer to the door electric lock to shorten the wiring distance. The cross-sectional area of the network cable is 0.2 square millimeters, which is 5 times smaller than our standard wire, so it is absolutely impossible, even if the distance between the controller and the electric lock is very short. The electric lock door magnetic signal line can be a network cable. Some people combine the four strands of the network cable to power the electric lock, although it is close to the norm in theory, it is not recommended. Doing so will cause other hidden dangers such as unstable connection terminals.

Stephanie Stephanie Stephanie Ellie Ellie Ellie Victoria Victoria Victoria Olivia Olivia Olivia Isabella Isabella Isabella Jayden Jayden Jayden Lucas Lucas Lucas Dylan Dylan Dylan Ryan Ryan Ryan Noah Noah Noah

Sweep the concern Yingze electronic official WeChat

x
Sample Apply
※ Please fill in your information, our company will deal with your problem as soon as possible.
主站蜘蛛池模板: 亚洲日韩男人网在线 | 欧美三级在线看中文字幕 | 久久国内免费视频 | 九九精品成人免费国产片 | 九一在线完整视频免费观看 | 国产黄色三级网站 | 黄色网址视频在线播放 | 久久99精品久久只有精品 | 国产精品伦子一区二区三区 | 91精品国产露脸在线 | 最近中文字幕免费完整 | 亚洲人成网站在线播放观看 | 97国产精品欧美一区二区三区 | 精品视频一区二区三区在线播放 | 亚洲国产91在线 | 国内精品久久久久香蕉 | 香蕉视频免费看 | 插入综合网 | 一区二区福利 | 成本人h片3d动漫网站在线看 | 国产美腿丝袜福利视频在线观看 | 久久97精品久久久久久久看片 | 国产91高清在线 | 制服丝袜手机在线 | 91尤物在线| 一区二区三区欧美 | 国产精品白嫩在线观看 | 国产精品成人免费福利 | 国产免费av片在线观看 | 亚洲乱码中文字幕综合 | 亚洲午夜精品一区二区 | 国产一级毛片亚洲久留木玲 | 亚洲综合色区图片区 | xxoo做爰猛烈动态视频网站 | 国产精品拍自在线观看 | 青青伊人久久 | 伊人久久在线观看 | 国产欧美日韩精品第二区 | 99久久精品国产片 | 亚洲成人在线播放视频 | 久久久夜色精品国产噜噜 |