Please do not use the Network Cable as the Cable for the Electric Lock to the Controller!
2016-11-08 16:52
Details of the problem:

Can the cable of the electric lock be replaced by a network cable?

Expert answer:

The line from the electric lock to the access control board in the access control construction looks very ordinary, but the irregular use of the line can easily cause the failure phenomenon that is difficult to find the cause, this must be paid attention to!

Due to the relatively large working current of various electric locks (compared to other devices in the access control system, such as access control board and access card readers), the electric locks are at a certain distance from the controller, and the voltage drop on the lock wires will be relatively large. If the pressure drop is too large, the electric lock will sometimes be able to move, sometimes not (such as the magnetic lock sometimes has insufficient suction). Shows that the door switch is abnormal. It may even grab current resources with the controller, making the controller insufficient power supply, restarting or even crashing.

Some engineers are convenient for wiring or purchasing, using network cables to wire the electric lock to the controller can easily cause malfunctions, although there seems to be no problem during debugging, problems will often occur after a period of time.

If the cable length from the electric lock to the controller is less than 50 meters, a two-core power cord with a cross-sectional area of 1.0 square millimeter is required, and no shielding is required, if it exceeds 50 meters, please double and add a two-core power cord for parallel power supply. If the cable length is greater than 100 meters, it is recommended to move the controller closer to the door electric lock to shorten the wiring distance. The cross-sectional area of the network cable is 0.2 square millimeters, which is 5 times smaller than our standard wire, so it is absolutely impossible, even if the distance between the controller and the electric lock is very short. The electric lock door magnetic signal line can be a network cable. Some people combine the four strands of the network cable to power the electric lock, although it is close to the norm in theory, it is not recommended. Doing so will cause other hidden dangers such as unstable connection terminals.

Stephanie Stephanie Stephanie Ellie Ellie Ellie Victoria Victoria Victoria Olivia Olivia Olivia Isabella Isabella Isabella Jayden Jayden Jayden Lucas Lucas Lucas Dylan Dylan Dylan Ryan Ryan Ryan Noah Noah Noah

Sweep the concern Yingze electronic official WeChat

x
Sample Apply
※ Please fill in your information, our company will deal with your problem as soon as possible.
主站蜘蛛池模板: 国产大学生毛片一级高清| 日韩免费看| 免费黄色网页| 国产在线观看午夜不卡| 黄片毛片免费| 182tv成人午夜在线观看| 日韩免费观看视频| 在线观看国产三级| 免费看a级毛片| 国产91精品高跟丝袜在线| 国产精品91在线播放| 国产小视频91| 久久午夜青青草原影院| 亚洲短视频在线观看| 182福利视频在线观看黄| 九九久久国产精品免费热6| 日本高清αv毛片免费| 亚洲一级毛片中文字幕| 成人二区| 色网站网址| 免费日韩在线| 欧美日韩a级a| 国产精品免费精品自在线观看| 国产chinese在线视频| 久cao在线香蕉69影院| 亚洲国产七七久久桃花| 中文乱码一二三四有限公司| 一区二区网站在线观看| 大陆三级特黄在线播放| 日本在线亚洲| 日本一级大黄毛片一级| 日韩一级a毛片欧美区| 日韩免费视频一区二区| 日韩特黄| 日产一区日产2区| 日韩免费视频观看| 日本理论在线观看被窝网| 日韩高清在线免费观看| 日韩a级毛片| 日本一级毛片视频网站| 久久黄色网|